Description
Front view and section of a head of wall firestop joint where a two hour rated metal stud wall meets concrete over metal deck, showing mineral wool compressed into the flutes, firestop joint spray, continuous galvanised angle and slotted track. Drawn to UL system HW-D-0042. A free AutoCAD DWG file download.